15 Technical data

Connections
Zones (max. 10 x): end of line 4k7; alarm resistor 1k; maximum 0.1 A
External operating panel (max. 2): 3-wire, maximum length 150 m for 1.5 mm²
Siren loop (2x): end of line 1k; maximum 0.7 A
Aux. output (1x): 18.5 V - 28.5 V; maximum 0.5 A
Relay contacts (3x): switch-over contact, maximum 30 V DC / 1 A
Optional relay contacts (8x): switch-over contact, maximum 30 V DC / 1 A
Power
Fuse: T1A 250 V
Voltage: 18.5 V - 28.5 V
Current: 2 A including battery charging current – charging current is interrupted if the control
panel is in alarm state
Battery capacity: 1.2 Ah to 7.2 Ah
General
Power supply: 230 V~ ±10% 50 / 60 Hz
Power consumption: 7 W to 60 W
Dimensions: 340 x 266 x 93 mm (width/height/depth) including protruding parts
Housing: ABS V0
Protection rating: IP30
Colour: RAL 7004
Operating temperature: -5 °C to 40 °C
Relative humidity during operation: 0% to 95%