{카테고리_이름} Argina CM+에 대한 설치 지침 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Argina CM+ 20 페이지. Conventional fire alarm control panel
7 24 V output
External devices can be connected to this output.
The output is electronically secured and the maximum permitted current is 500 mA.
The precise way the output operates can be altered by using the CMPlus.exe program. For
example, it can be arranged that the 24 V output is interrupted when the fire alarm control panel
is reset, e.g. for supplying and resetting beam detectors.
8 Relay output
The standard configuration is 3 potential-free relays, each of which can switch 30 V / 1A.
They are freely configurable using the CMPlus.exe program.
Caution: a relay programmed as a fault output is normally always closed. If a fault occurs or the
control panel fails completely, then the relay is de-energised.