9.2 Configure display (optional)

► Select [Uni] and set the unit of measurement:
- [bAr], [mbAr],
- [MPA], [kPA],
- [PSI],
- [inHG],
- [iH2O],
- [mmWS]
The selectable units of measurement depend on the respective unit.
► Select [diS] and set the update rate and orientation of the display:
- [d1]: update of the measured values every 50 ms.
- [d2]: update of the measured values every 200 ms.
- [d3]: update of the measured values every 600 ms.
- [rd1], [rd2], [rd3]: display as for d1, d2, d3; rotated by 180°.
- [OFF ] = The display is switched off in the operating mode. When one of the buttons is pressed, the current
measured value is displayed for 30 s.
The LEDs remain active even if the display is deactivated.
Even with unsteady pressure characteristics [d1] provides optimum readability;
the corresponding algorithms are stored!

9.3 Set output signals

9.3.1 Set output functions

► Select [ou1] and set the switching function:
- [Hno] = hysteresis function/NO,
- [Hnc] = hysteresis function/NC,
- [Fno] = window function/NO,
- [Fnc] = window function/NC.
► Select [OU2 ] and set the analogue function:
- [Hno] = hysteresis function/NO,
- [Hnc] = hysteresis function/NC,
- [Fno] = window function/NO,
- [Fnc] = window function/NC.
- [I] = current signal 4 ... 20 mA,
- [U] = voltage signal 0 ... 10 V.

9.3.2 Define switching limits for the hysteresis function

► [ou1] / [ou2] must be set as [Hno] or [Hnc].
► Select [SPx] and set the value at which the output is set.
► Select [rPx] and set the value at which the output resets.
rPx is always smaller than SPx. The unit only accepts values which are lower than the value for SPx.

9.3.3 Define switching limits for the window function

► [ou1] / [ou2] must be set as [Fno] or [Fnc].
► Select [FHx] and set the upper limit value.
► Select [FLx] and set the lower limit value.
FLx is always lower than FHx. The unit only accepts values which are lower than the value for FHx.

9.3.4 Scaling of the analogue value

► Select [ASP2] and set the value at which 4 mA / 0 V is provided.
► Select [AEP2] and set the value at which 20 mA / 10 V is provided.
Minimum distance between ASP2 and AEP2 = 20 % of the measuring span (scaling factor 5).