Digitus Biometrics db Enline 설치 및 사용자 설명서 - 페이지 4
{카테고리_이름} Digitus Biometrics db Enline에 대한 설치 및 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Digitus Biometrics db Enline 10 페이지.
INSTALLATION THE db ENLINE UNIT
It's important to record the serial number and location of each db Enline Unit installed. The db
Enline's serial number is used to identify it within the Digitus DAS-SQL software.
There is no limit to the number of db Enline units that can be installed on a db Bus, as long as:
Typically one db Enline Unit would be installed at the end of each row of cabinets.
The Enline unit comes in two parts, the front section and the back section.
Locate a suitable mounting surface for the db Enline unit. This would typically be on the end of a
row of cabinets. A person using the db Enline unit should be able to stand directly in front of the
unit without obstruction.
• Use the enclosed mounting template to mark the location for the mounting and cable
pass-through holes. Ensure the template is level prior to marking by using a torpedo level.
It is highly recommended that the side panel be removed from the cabinet and the drilling be done
outside of the data center. This will prevent the possibility of any metal shavings being drawn into
• Drill the cabinet where the 4 mounting screws are to be fixed.
P a g e | 3
(db Enline Units + Remote Nodes <= 32)
Front Section
electrical equipment.
Back Section
Model: db Enline