Installation Instructions
HLF LED
Driver Access
**THE FIXTURE SHOULD NOT BE ENERGIZED DURING ANY ELECTRICAL WORK**
The driver is pre-wired so access to the driver during installation is unnecessary. Open the fixture by loosening the four hex key screws on the
driver box cover and rotate the driver box cover away from housing to open. Ensure the fixture is not energized and disconnect the electrical
connectors to the affected driver. Remove the three slotted hex screws holding the driver to the driver box cover. Remove the two slotted hex
screws holding the driver to the bracket. Attach new driver with two slotted hex screws torqued to 24 in-lbs(2.7N-m). Reattach electrical con-
nectors. Check gasket on driver box for misalignment and correct as necessary. Rotate the driver box cover closed and tighten the six hex key
screws (50 in.-lbs) EVENLY.
Shielding Options: The doorframe can be opened with any of the shielding options attached. Attach with the 8-32 thread forming screws
provided. Holes will be provided in the doorframe. Should the doorframe holes need be cleared for any reason, drill no deeper than 1/2" with a
.147" (#26) diameter drill.
UPPER or BOTTOM VISOR (UBV)
VANDAL GUARD (VG)
Troubleshooting: If this fixture fails to operate properly, check to make sure: • The fixture is wired correctly.
voltage at the fixture is correct. If all these variables have been checked and the fixture still does not operate as specified, contact your local Lithonia Lighting
distributor.
Lithonia Lighting Outdoor • One Lithonia Way • Conyers, Georgia 30012
Phone: 800-279-8041 • Fax: 770.918.1209 •
© 2012 Acuity Brands Lighting, Inc. All rights reserved. Rev. 3/13
FULL VISOR (FV)
WIRE GUARD (WG)
• The fixture is grounded correctly.
www.lithonia.com
• The line
Part Number: RJ521380 Rev B