Acuity Controls ECLYPSE A1000 설치 매뉴얼 - 페이지 8

{카테고리_이름} Acuity Controls ECLYPSE A1000에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Acuity Controls ECLYPSE A1000 10 페이지. Asset tracking
Acuity Controls ECLYPSE A1000에 대해서도 마찬가지입니다: 설치 매뉴얼 (14 페이지)

Acuity Controls ECLYPSE A1000 설치 매뉴얼
5.0 - Configuring the Controller
The controller's factory-default hostname is
eclypse-xxxxxx.local where xxxxxx is the last 6 characters
of the MAC address printed on a sticker located on the
side of the controller. See Figure 11.
For example, the sticker on the side of a controller
shows that its MAC address is 76:a5:04:cd:4a:d1.
Connect to the controller's Web interface as follows:
1. Open your Web browser.
2. In the Web browser's address bar, type
https://eclypse-cd4ad1.local
3. Login to the controller. Then set the controller's
parameters in the controller's configuration Web
interface. See Connecting to the Controller's
Configuration Web Interface.
5.2 Using the Controller's IP Address in a
Web Browser
Connect to a controller through its IP address as follows:
For a Wi-Fi Network Connection:
1. Open your Web browser.
2. In the Web browser's address bar, type
(the controller's factory-default wireless hotspot IP
address) and click go.
3. Login to the controller. Then set the controller's
parameters in the controller's configuration Web
interface. See Connecting to the Controller's
Configuration Web Interface.
For an Ethernet Network Connection: You must know
the controller's current IP address (from the DHCP server
for example).
1. Open your Web browser.

6.0 - Additional Information

6.1 Maintenance
Turn off power before any kind of servicing.
Regular Maintenance
Each controller requires minimal maintenance, but it is
important to take note of the following:
Clean the outside of the controller by polishing it
with a soft dry cloth.
Retighten terminal block connector screws annually
to ensure the wires remain securely attached.
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2017-2019 Acuity Brands Lighting, Inc. All rights reserved. 03/29/19
and click go.
192.168.0.1
2. In the Web browser's address bar, enter the
controller's IP address and click go.
3. Login to the controller. Then set the controller's
parameters in the controller's configuration Web
interface. See Connecting to the Controller's
Configuration Web Interface.
5.3 Connecting to the Controller's
Configuration Web Interface
Figure 13: Web Interface Login
At the first connection to an ECLYPSE Controller you will
be forced to change the password to a strong password
for the admin account to protect access to the
controller.
In Network Settings, configure the controller's network
parameters so that they are compatible with your
network. It is important to create new user accounts with
strong passwords to protect the controller from
unauthorized access. Remove the factory default admin
account as this is a commonly known security breech
(only the password for this user account needs to be
compromized)
6.2 Disposal
The Waste Electrical and Electronic Equipment (WEEE)
Directive sets out regulations for the recycling and dis-
posal of products. The WEEE2002/96/EG Directive ap-
plies to standalone products, for example, products that
can function entirely on their own and are not a part of
another system or piece of equipment.
For this reason Acuity products are exempt from the
WEEE Directive. Nevertheless, Acuity products are
marked with the WEEE symbol , indicating devices are
not to be thrown away in muncipal waste.
Products must be disposed of at the end of their useful
life according to local regulations and the WEEE
Directive.
A1000AT_IG_10_EN
8 of 10