2. Save CXC text file if necessary.
Bypass system LVD by setting override switch
CAUTION: If the LVD is not bypassed, the DC loads will be shut down when the wiring to the
controller is removed. Remove the DB connectors from I/O Terminal Block
3. Standard Customer Connections on the I/O terminal block for the 1.8kW Shelf:
P3 JUMPER SETTINGS (FOR LVD CONTROL INHIBIT FUNCTION):
SHORT PINS 1 AND 2 IF LVD IS CONTROLLED ON K1-NC CONTACTS TO MAINTAIN OPERATION.
SHORT PINS 2 AND 3 IF LVD IS CONTROLLED ON K1-NO CONTACTS TO MAINTAIN OPERATION