FOR AUTHORIZED SERVICE PERSONAL ONLY
TOSHIBA/HOUSTON INVERTER PLANT
DESIGN DATA
SUBJECT:
1000 Series UPS Options - Frequency Conversion
Setup:
1. Make sure the UPS is off and the AC Line is on. The LCD screen should appear
blank.
2. Press and hold the function button for 1 second and release the button to enter the
front panel settings. Once in this mode, you can scroll through different settings
using the function button.
3. Look for the newly added software, "Freq Convert Set" and press Enter.
4. Once inside, you can change the output frequency by pressing the function button.
5. After choosing the correct frequency, press Enter to select it. Once selected, the
LCD will display a blank screen.
6. Turn on the UPS.
Note:
1
If the communication fails during "Programming" for:
• R Mask – user should wait more than 35 seconds and then click the "W" button on
the Toolbar to start "Programming" again.
• B Mask – The LED labeled Alarmed_LED will be turned on. The user should wait
more than 10 seconds and then click the "W" button on the Toolbar to start
"Programming" again.
2
Do not run any other application software on the PC during "Flash Process", because the
"FlashH08" application uses up a large amount of the PCs resources.
NO.
REVISION
D-UM0029 Page 4 of 4
DATE