Toshiba 2000 사용자 설명서 - 페이지 39

{카테고리_이름} Toshiba 2000에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Toshiba 2000 49 페이지. Integrated controller, cif module
Toshiba 2000에 대해서도 마찬가지입니다: 빠른 참조 매뉴얼 (2 페이지)

Toshiba 2000 사용자 설명서
Chapter 7 Maintenance

7.2 Checking the Status Information

When there is an error in the CIF module, an error code is stored in the CIF module
internal status (0W).
Status
RDY ERR
[0W]
Error
code
01H
02H
03H
04H
05H
10H
26
F
E
D
C
B
No use
Bit
Name
F
RDY
1:Normal operation
ready
0:Initializing or error occuring
E
ERR
1:Error
error
0:No error
Type
CPU error
CPU error has been detected
during initialization.
ROM error
ROM error has been
detected during initialization.
Work RAM error
RAM error has been detected
during initialization.
Common memory
Common memory error has
error
been detected during
initialization.
Switch setting error
Switch setting error has been
detected during operation.
WD timer error
Watchdog timer error has
been detected during
operation.
A
9
8
7
6
Description
Description
model 2000 CIF Module (CF611)User's Manual
5
4
3
2
1
Error code
Status
Replace the CIF module.
・ ERR bit turns ON.
・ Module operation is
stopped.
Press the reset button and
check whether recovery is
possible. If it still occurs,
replace the CIF module.
・ ERR bit turns ON.
・ Module operation is
stopped.
0