ECI 1000-U LCD 설치 매뉴얼 - 페이지 15
{카테고리_이름} ECI 1000-U LCD에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. ECI 1000-U LCD 18 페이지.
NOTE: The heavy door closing speed must be set slower than a standard door to
comply kinetic energy requirements set by the Elevator Codes.
NOTE: Must press ESC button to save all changes into permanent memory. Failing
to do so will result in parameters reverting to default settings in the event of a
power loss.
8.2.4 Door Closing Force Adjust
1. Set the TEST/RUN switch to the TEST position.
2. Set the doors to fully OPEN
3. Select EDIT PARAMETERS menu then select CCL parameter.
4. Set the OPEN/CLOSE switch to the CLOSE position and adjust the CCL parameter until the
closing force is below the 30lbs maximum allowed by code as measured by an approved gauge
per manufacturer's specifications and directions.
5. Perform several open/close cycles then recheck force to insure force is still within code.
6. Once closing force is set within specifications, be sure to press ESC button to return to main
menu.
8.3 RUN Operation
1. Put the TEST/RUN switch in the TEST position.
2. Put the OPEN/CLOSE switch in the center position
3. Go to EDIT PARAMETERS menu and select Input Voltage.
4. Set the Input Voltage parameter to the voltage of the controller inputs that will be present at
connector X13. These inputs are AC/DC compatible.
5. After entering the proper voltage press the ENTER key then the ESC key to return to MAIN
menu.
6. Connect controller inputs to X13
7. Put TEST/RUN switch in the RUN position and perform several OPEN and CLOSE cycles to
verify proper operation.
ECI 1000-U LCD Installation Manual
Electronic Controls, Inc.
7073 North Atlantic Ave. Cape Canaveral, FL 32920
800-633-9788
www.eciamerica.com
P a g e
| 15