Arico TC5E 사용자 설명서 - 페이지 8

{카테고리_이름} Arico TC5E에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Arico TC5E 20 페이지. Hot-runner temperature controller

Arico TC5E 사용자 설명서
+1 sec: The alarm output function disable or enable select (when
1-4-5 Soft start (Heater dehumidify) function
To avoid the humidity make the heater burn out. The soft start function could
output a lower current to make dehumidify action when turn on the power.
Soft start condition:
The soft start percentage (
PV ; PV < 120°C,manual and PID tuning function are disable, the soft start
would be executed. Set
Soft start interrupt:
Soft start
1-4-6 PID auto tuning function
For get the optimal PID value in some system, it is possible to execute "PID
auto tuning" function when first use or heater system changed.
After finished auto tuning, the optimal PID would be save into the instrument
Start PID auto tuning function:
(1)PV must lowerthan120°C or 180°F
(2)SV must higher than PV for 80°C or 100°F
(3)Set parameter
PS:During PID auto tuning execution, the decimal point of PV would flash.
After instrument get the optimal PID, the decimal point turn off and
instrument recovery to auto temperature control.
A R ICO T echnology Co., L td.
power re-setting, the default setting is enable)
) and time (
to zero for disable soft start function.
into
). After power turn on, if SV >
+ 1 sec
Manual/Auto mode
-7-