Toshiba Carrier MCY-MAP0367HS-UL 설치 매뉴얼 - 페이지 7

{카테고리_이름} Toshiba Carrier MCY-MAP0367HS-UL에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Toshiba Carrier MCY-MAP0367HS-UL 30 페이지. Outdoor unit

Toshiba Carrier MCY-MAP0367HS-UL 설치 매뉴얼
 Necessary space for installation
(Unit: in (mm))
Obstacle at rear side
Upper side is free
1. Single unit installation
2. Obstacles on both right and left sides
The height of the
obstacle should be
lower than the height
of the outdoor unit.
11.8" (300)
5.9" (150)
or more
or more
3. Serial installation of two or more units
The height of the obstacle should be lower than the
height of the outdoor unit.
5.9" (150)
11.8" (300)
11.8" (300)
11.8" (300)
or more
or more
or more
or more
Obstacle also above unit
7.9" (200)
or more
EN-11
Obstacle in front
Above unit is free
1. Single unit installation
2. Serial installation of two or more units
Obstacle also above unit
39.4" (1000) or more

Obstacles in both front and rear of unit

Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit, should be lower than the height of the outdoor unit.
Standard installation
1. Single unit installation
2. Serial installation of two or more units
11.8" (300)
or more
 Installation of outdoor unit
• Before installation, check the strength and leveling of the base so that abnormal sounds do not emit from the unit.
• According to the following base diagram, secure the base firmly with the anchor bolts.
(Anchor bolt, nut: 0.4" (M10) x 4 pairs)
7.7" (195)
– 6 –

Serial installation in front and rear

Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit should be lower than the height of the outdoor unit.
Standard installation
39.4" (1000)
11.8" (300)
59.1" (1500)
or more
or more
or more
11.8" (300)
or more
Back side
Drain hole
22.6" (574)
24.4" (620)
7.7" (195)
Drain hole
Drain hole
Drain hole
Front side (Air discharge side)
Installation Manual
78.7" (2000)
7.9" (200)
or more
or more
EN-12