Toshiba Carrier MMD-AP0094SPH2UL 설치 매뉴얼 - 페이지 15

{카테고리_이름} Toshiba Carrier MMD-AP0094SPH2UL에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Toshiba Carrier MMD-AP0094SPH2UL 44 페이지. Air conditioner multi type

Wire connection
REQUIREMENT
• Connect the wires matching the terminal numbers.
Incorrect connection causes a trouble.
• Pass the wires through the bushing of wire connection
holes of the indoor unit.
• The low-voltage circuit is provided for the remote
control. (Do not connect the high-voltage circuit)
• Remove the underside cover plates (2 plates).
Remove the two screws from the electrical control
box cover and then remove the cover from the hook
on which it is hanging.
• Remove the conduit plate from the side plate and
attach the conduit to the conduit plate.
Next, attach the conduit plate to the side plate.
• Tighten the screws of the terminal block, and fix the
wires with cord clamp attached to the electrical
control box.
(Do not apply tension to the connecting section of the
terminal block.)
• Mount the cover of the electrical control box without
pinching wires.
Electrical control box
Conduit plate
Remove
cover plate
Bushing of control
Conduit
and remote
Conduit
plate
control wires
27-EN
Electrical control box cover
fixed screw
Electrical control box
cover
Hook
Power supply wire
Remote
Cord clamp
and ground wire
control wire
Control
wire (2-
core
shielded
wire)
Cord
clamp
Ground
screw
L
L
B A
Power supply wires and
ground wire
1
Strip the wire ends.
Power supply wire: 0.4" (10 mm)
Ground wire: 0.8" (20 mm)
2
Match the wire colors with the terminal
numbers on the indoor units' and circuit
breakers' terminal blocks and firmly screw
the wires to the corresponding terminals.
3
Secure the ground wire with the ground
screw.
4
Fix the wires with a cord clamp.
Unit: in (mm)
0.8" (20)
1.2" (30)
L
L
1
2
0.4" (10)
Ground wire
CAUTION
Firmly tighten the screws of the terminal block.
Keep the wire length as shown in figure below when it
is connected to the terminal block.
Power supply wires and control
wire
– 14 –

Address setup

Set up the addresses as per the Installation Manual
supplied with the outdoor unit.
EN
28-EN