5

OFF timer operation

Off timer
You can set the timer to the time at which to stop operation of an air conditioner.
NOTE
• The air conditioner stops operating after the time set in "Off timer" has elapsed.
• In the period until the air conditioner operation is stopped by the "Off timer", countdown of the "Off timer"
continues even if the air conditioner is stopped and started.
Countdown of "Off timer"
Operating
Set "Off
Stopped
timer"
manually
17-EN
1
In "Menu", select "Timer", and press
[ 
Set/Fix]
2
Press [ 
 ] and [ 
 ] to select the off timer
3
Press [ 
Set/Fix]
1
In the "Off timer" screen, press [ 
to select "Off timer"
2
Press [ 
 ]
Pressing [ 
 ] cancels the settings.
3
Press [ 
 ] and [ 
 ] to select "Timer"
4
Press [ 
 ] and [ 
 ] to change the time
The time can be set in 30 minute intervals for up
to 24 hours, and at 1 hour intervals after that.
5
Press [ 
Set/Fix]
Return to the "Timer" screen.
Stop
Operating
Stop
Operated
No time remaining in
manually
"Off timer"
─ 9 ─
6

Installation

Location
Avoid locations where inside the ceiling is used as a route for outside air.
Install the Outside Air Unit considering a discharge port position. The Outside Air Unit has a different discharge
temperature compared with the indoor unit for air conditioner.
Avoid installing near machines emitting high frequency waves.
Not suitable for chemical plants such as liquefi ed carbon dioxide refrigerant plants.
Do not install the air conditioner in locations where iron or other metal dust is present. If iron or other metal dust
adheres to or collects on the interior of the air conditioner, it may spontaneously combust and start a fi re.
A failure may occur in certain locations such as the following:
Areas with large amount of oil droplets (including machine oil) or vapors
Salty areas near oceans, etc.
Hot springs emitting sulfi dizing gas, etc.
Heavily acidic or alkaline places.
 ] and [ 
 ]
Special maintenance or parts are required for use in the above places. For details, contact the dealer where you
purchased the product.
Leave an enough space around the air intake and discharge of the outdoor unit so that the ventilation is not
restricted.
Avoid places where strong wind may blow against the air intake and discharge of the outdoor unit.
Attach a snow stand, snow hood, etc. to the outdoor unit for use in snowfall areas. For details, contact the dealer
where you purchased the product.
Make sure drain water from the outdoor unit is emitted into places with good drainage.
Make sure the long life prefi lter and high-effi ciency fi lter are installed in the fi lter chamber. If the long life prefi lter
and high-effi ciency fi lter are not attached, heat exchangers etc. clogged with dust can result in water leakage.
Attach the long life perfi lter and high-effi ciency fi lter because dust can also get into the area being air conditioned.
Keep a distance of at least 1 m between the air conditioner / remote controller and a TV or radio. Failure to
observe this precaution may cause visual disturbance or noise.
Leave a distance of at least 1.5 m between the air discharge and a fi re alarm. If this precaution is not observed,
the alarm may not work properly or detect fi re in case of fi re.
Be careful of operation sounds
Locate the unit in a place secure enough so that the sounds and vibrations do not increase.
If something is placed near the air discharge of the outdoor unit, noise may increase.
Be careful not to disturb your neighbors with cool / warm air or noise coming from the air discharge of the
outdoor unit.
18-EN