Architectural Air Curtains
Models :
ARC10E, ARC15E, ARC20E, ARC10W, ARC15W, ARC20W,
ARC10WLT, ARC15WLT, ARC20WLT, ARC10A, ARC15A & ARC20A
IMPORTANT: THESE INSTRUCTIONS SHOULD BE READ CAREFULLY AND RETAINED FOR FUTURE REFERENCE
IMPORTANT SAFETY ADVICE
DO NOT COVER OR OBSTRUCT the air inlet or
outlet grille.
ENSURE THE APPLIANCE IS EARTHED.
Do not use this product in areas where excessive
dust exists.
Do not use this product with young children
unattended.
This appliance is not intended for use by children
or other persons without assistance or supervision
if their physical, sensory or mental capabilities
prevent them from using it safely. Children should
be supervised to ensure that they do not play with
the appliance.
The product carries the Warning symbol
indicating that it must not be covered.
Warning: In order to avoid overheating, do not cover
the product.
This product must not be located immediately above
or below a fi xed socket outlet or connection box.
Always disconnect supply before working on the
product.
This appliance should only be connected to the fi xed
wiring of the premises by means of conduit.
This product should be mounted safely to solid wall,
fl oor or ceiling surfaces only.
If mounting the appliance horizontally it should not
be mounted less than 1.8m from the fl oor.
This product must not be subjected to water spray
or immersion.
Ensure the supply cables are of adequate current
carrying capacity and are protected by a suitable
fuse.
This appliance should not be mounted in a toilet or
washroom.
Ensure proper manual handling procedures are
observed at all times.
This appliance is not intended for use by persons
(including children) with reduced physical, sensory
or medical capabilities, or lack of experience or
knowledge, unless they have been given supervision
or instruction concerning use of the appliance by a
person responsible for their safety.
This product is not equipped with a device to control
the room temperature. Do not use this product in
small rooms when they are occupied by persons
not capable of leaving the room on their own, unless
constant supervision is provided.
WARNING: Isolate electrical supply to ALL modular
linked units when carrying out maintenance.
Models
Heat
Electrical
output
Model
kW
AMBIENT
ARC10A
220-240V ~1PN
n/a
ARC15A
220-240V ~1PN
n/a
ARC20A
220-240V ~1PN
n/a
ELECTRICALLY HEATED
ARC10E
6.0 / 12.0
380-415V ~3PN
ARC15E
9.0 / 18.0
380-415V ~3PN
ARC20E
12.0 / 24.0
380-415V ~3PN
WATER HEATED (at 60/40, 55/45, 45/35 °C - LPHW)**
ARC10WLT
12
220-240V ~1PN
ARC15WLT
18
220-240V ~1PN
ARC20WLT
24
220-240V ~1PN
WATER HEATED (at 82/71 °C - LPHW)**
ARC10W
17
220-240V ~1PN
ARC15W
24
220-240V ~1PN
ARC20W
34
220-240V ~1PN
Standard Units Only
*
See separate specifi cation sheet from Dimplex
**
Electrical
The installation of this appliance should be carried out by a
competent electrician and be in accordance with the current IEE
wiring regulations.
Fixing Positions
This appliance may be either fi xed to a ceiling - see Fig. 1 or fl oor
mounted see Fig. 2 using an appropriate foot.
A minimum distance of 500mm is required from top of the appliance
to the ceiling (see Fig. 1) and also the distance between the
bottom of the appliance and the top of the door should be kept to
a minimum (see 'C' in Fig. 1).
This appliance should not be mounted less than 1.8mt. from the
fl oor.
To open the appliance, remove the inlet grilles ('x' in Fig. 3)
Remove the front panel ('z' in Fig. 3).
Horizontal Mounting
By using the fi xing holes in the top of the air curtain, attachment
to a ceiling over the product can be achieved using suitable M10
threaded steel rod or similar supports of suffi cient strength - see
's' in Fig. 1.
Vertical Mounting
The architectural range of air curtains can be vertically mounted
using a suitable fl oor foot (Ref: ARCVMF). Contact Dimplex or
your service agent for further information. Refer to Fig. 2 for
fi xing details.
Electrical
Weight
*
Supply
load
kg
(per phase)
A
1.5
55
2.3
82.5
3.0
110
18
60
27
90
36
120
1.5
65
2.3
95
3
130
1.5
65
2.3
95
3
130
Recom-
mended
height
m
3.75
3.75
3.75
3.75
3.75
3.75
3.75
3.75
3.75
3.75
3.75
3.75