q)  Horn adapter ST–G1 (ULM–53L–02) and 
ST–G1,5  (ULM–53L–06)  for  improved 
transmitted signal reception can be used in 
open channels, sumps, tanks, etc.
r)  Horn adapter increases the radiation direc-
tivity of acoustic waves, improves reception 
of  weak  echoes  (unstable  level  surfaces, 
solid materials, etc.) and reduces the risk 
of false reflections.
s)  The horn adapter is installed to level meters 
via  process  connection  G1"  (ST–G1)  or 
G1½" (ST–G1,5).
8 .  e
lectrical
ULM–53L–__–I and ULM–53L–__–U
The ultrasonic level meter is designed to 
be connected to supply unit or to control-
ler  through  two  or  three-wire  5  m  long 
cable.  Connection  diagram  as  shown  in 
Fig. 14 and 15.
„ULM–53L–__–M"
The  connection  is  done  by  means  of 
shielded  four  wires  cable  directly  into  a 
binary input of control system (RS–485). 
Connection diagram as shown in Fig. 16. 
Shielded cable length is 5 m. 
Legend:
BK – Black
WH – White
BU – Blue
YE – Yellow
BN – Brown
GN – Green
Make the electric connection in voltage-free state!
In case of strong electromagnetic interferences (EMI), parallel cable ducting with power lines, or when
cable length exceeds 30 m we recommended to use shielded cable (for "I" and "U" variants only).
10
connection
Horn adapter ST
Fig. 13: Horn adapter installation
Fig. 14: Level meter connection diagram
(Variant – I)
Fig. 15: Level meter connection diagram
(Variant – U)
Fig. 16: Level meter connection diagram
(Variant – M)
ULM–53L
© Dinel, s.r.o.