ABB 88TK50-E/R1210 모듈 및 애플리케이션 설명
Station protocol control operating
Diagnosis register 246
using module address 62
Bit
Type
15
S
Module address code (A = 0 = 60, B = 1 = 61)
14
S
Signal simulated
Protocol error AS detected
13
D
Channel code, 0 = single ---channel, 1 = dual---channel
12
S
Partner module fault
11
S
10
0
9
D
Module restart executed
8
S
Module from AS bus disconnected
7
S
Operating mode setting wrong
Checksum error detected
6
S
Station mod. arrangem. changed
5
S
4
Telegram error in AS detected
D
3
D
Cycle abortion detected
Protocol error remote bus detected
2
D
Response from module missing
1
D
0
0
Station protocol control
not accessible from bus
Voltage monitoring responded
Wrong firmware PROM
Hardware defect
S = Static annunciations disappear automatically upon deactivation
D = Dynamic annunciations are cancelled after the contents of the diagnosis register has been transmitted
0 = Not used
= For cause and associated module address cf. background diagnosis register, Figures 3 to 5
= For cause cf. background diagnosis register, Figures 3 to 5
= Also causes the output of CDS message "AS restart executed"
= Also causes the output of CDS message "Response from AS missing"
= Cause of the fault on other module; only SG lamp of disturbed module is illuminated
Figure 2: 88TK50 diagnosis messages using module address 62
>
1
=
>
1
=
>
1
=
4410
4204
88TK50/R1210
CDS
messages
4430
4412
4424
4415
4416
4423
4419
4425
4417
4428
4427
4418
ST
SG
1
>
=
SST
SSG