Ariston STI ProTech 125 설치 및 사용 설명서 지침 - 페이지 20

{카테고리_이름} Ariston STI ProTech 125에 대한 설치 및 사용 설명서 지침을 온라인으로 검색하거나 PDF를 다운로드하세요. Ariston STI ProTech 125 24 페이지. Unvented hot water storage cylinders

www.tradeplumbing.co.uk Call Sales On 08708034288
www.tradeplumbing.co.uk Call Sales On 08708034288
20
Unvented Controls(s)
Check controls as per the following:
1) Line strainer - with the water supply turned off remove screen from
strainer and clean of any detritus;
2) Expansion vessel - with the water supply turned off and taps open, check
expansion vessel pressure and top up as necessary;
3) Temperature & pressure relief valve - with the water supply turned on,
check manually by lifting the test lever/turning the test knob (ensure valve
closes after testing);
4) Expansion relief valve - check manually by turning the test knob (ensure
valve closes after testing);
5) Discharge pipes (D1) - from both temperature & pressure relief and
expansion relief valve for obstructions;
6) Tundish & discharge pipe (D2) - open either valve gradually to produce a
full bore discharge into tundish and D2 without any back pressure;
7) Pressure reducing valve - check that the correct outlet pressure is being
maintained by recording the pressure at an in-line terminal fitting i.e. tap.
Thermostats
Ensure that all thermostats adjusted for the correct temperature setting, this
should be between 60 and 65°C.
N
!
OTE
W
HERE THERE IS A POSSIBILITY OF SCALE FORMING
THE THERMOSTAT TO BELOW
,
IT IS RECOMMENDED TO ADJUST
60
O
C