ABB ACH550 series 빠른 시작 매뉴얼 - 페이지 6
{카테고리_이름} ABB ACH550 series에 대한 빠른 시작 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. ABB ACH550 series 6 페이지. Pumpsave 4.1, energy savings calculator for pump drives
ABB ACH550 series에 대해서도 마찬가지입니다: 사용자 설명서 (14 페이지), 설치, 운영 및 유지보수 매뉴얼 (18 페이지)
Step 2: Navigate to parameters on the control panel (ACH-CP-B), changed parameters and record all changed
parameters.
Step 3: If there is a fieldbus adapter, such as Lon communications, navigate to group 51 and record all settings in this
group.
Step 4: If there were embedded fieldbus communications, such as BACnet, navigate to group 53 and record all settings
in this group.
Step 5: Navigate to parameter 99.02 to record macro setting in the drive programming.
*Note that the base programming for the drive will depend on the macro loaded, so the changed parameters will not
reflect a parameter that is part of the default of the macro. Reference the ACH550 manual for macro parameter
defaults.
Option B: Gathering the programming data – Drive Windows Light
Step 1: Connect Ethernet cord to RJ45 connector in 64652745 (OPEX-01 Interface Board) and serial to USB converter to
your computer. Ensure that drivers are configured and open Drive Windows Light on your computer.
Step 2: In Drive Windows Light you can actively navigate to parameters or create a backup of the drive programming on
your computer.
Step 3: Ensure that you have the changed parameters, Group 51 settings, Group 53 settings, as well as parameter 99.02
for to identify the macro setting in the drive programming.
*Note that the base programming for the drive will depend on the macro loaded, so the changed parameters will not
reflect a parameter that is part of the default of the macro. Reference the ACH550 manual for macro parameter defaults
This solution will support frame sizes 1 through 6. For frame sizes 7 and 8 the 64652745 (OPEX-01 Interface Board) and
64738852 (Connection Cable) is already installed on the control board (SMIO-01) board and will be able to be removed
with the control board (SMIO-01).
Through the removal of the control board (SMIO-01) there are two options in interfacing with the previous programming
for the drive. The information that is gathered from the changed parameters list, the communications settings in group
51 group and 53, as well as understanding which macro is being used provides the Technician with all the critical data to
be confident that they have the information needed to program the replacement ACH580 drive correctly. By backing
these up to a panel or to a computer file using Drive Windows Light it provides a fast way to support the programming
of the replacement ACH550.
LVD-EOTKN094U-EN REV A
Effective: 2022-06-30
6