Connection procedure with VFD cable
For connection procedure with conduits, see
1.
Attach a residual voltage warning sticker in the local language.
2.
Frames R6 and R8: Remove the shroud on the power cable terminals.
Frame R8: For easier installation, you can remove the side plates.
R6
R6
3.
Prepare the power cables:
Remove the rubber grommets of the cables to be installed from the cable entry plate. Remove the unused grommets
and reinstall with the cone pointing down (3a).
Cut a sufficient hole in the rubber grommet. Slide the grommet onto the cable (3b) with the remaining cone pointing
down.
Prepare the ends of the input power cable and motor cable as illustrated in the applicable figure (3c).
Slide the cables through the holes in the cable entry and attach the grommets to the holes.
3a
4.
Connect the power cables. For the tightening torques, refer to
Ground the shield 360 degrees by tightening the clamp of the power cable grounding shelf onto the stripped part of
the cable (4a).
Connect the twisted shield of the cable shields to the grounding terminals (4b).
Frame R8: to install the common mode filter, see
Connect the phase conductors of the motor cable to the T1/U, T2/V and T3/W terminals. Connect the phase
conductors of the input power cable to the L1, L2 and L3 terminals (4c).
Tighten the screws to the torque given in the installation drawing below.
R3
1.7 N·m
L1, L2, L3, T1/U, T2/V, T3/W: 1.7 N·m (15 lbf·in)
Connection procedure with conduit
PE
3c
3b
Related documents
1.7 N·m
4a
1.7 N·m
(15 lbf·in)
.
R8
R8
Terminal
data.
.
4c
4b
R8
PE
1.7 N·m