FirePro 08100 매뉴얼 - 페이지 9

{카테고리_이름} FirePro 08100에 대한 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. FirePro 08100 10 페이지.

FirePro 08100 매뉴얼
Servicing & Maintenance
7
The FirePro Suppression system should be serviced at least every 6 months in accordance with
AS 1851, more often in aggressive environments. Periodic visual inspections of the installed
system must also be conducted by the operators to ensure all installed parts are free from
debris, rust, or electrical faults.
accredited service technicians.
NO PERSONNEL SHOULD BE IN THE RISK AREA DURING TESTING
Servicing and Maintenance Procedure
Disconnect the FirePro activation circuit (Yellow) at the panel, and
1.
connect the FirePro simulator.
Visually inspect all installed FirePro Generators, cable, connections,
2.
detection devices and siren/strobes. Look for any signs of damage or
wear and replace as necessary.
Test the function of all connected detection devices. Testing method will
3.
depend on the specific device, check product manual if unsure.
Test the function of the siren/strobe by putting the detection circuits into
4.
alarm and ensure that the siren/strobe can be heard and is illuminated.
Activate the system – after ensuring the FirePro Simulator is connected.
5.
FirePro Simulator stay illuminated until the reset button on the simulator is pressed.
Reconnect the FirePro activation circuit.
6.
System Logbook
A logbook recording all the relevant events concerning the installation. The logbook contains
the items required that provide for the recording of all events during the life of the installation.
Content of logbook:
Devices used
Date of each inspection
Comments re outcome of each inspection

Specifications

8
Size of Dash Panel
Size of Dash Cutout
Max Number of FirePro Units
Power Supply
Fuse for Power Supply
Max of Linear Heat Detection
Six Monthly servicing must only be undertaken by
UNTIL THE FIP IS FULLY ISOLATED
125mm (w) x 95mm (h)
105mm (w) x 68mm (h) Min clearance behind Panel 80mm
12v - 2 FP Units
12-24vDC
5A
50m
In the appendices of the Logbook:
Schematic diagrams
Photos of the Original FirePro Installation
Inspection reports
24v – 4 FP Units
Control Panel
Model 08100
Rev 4.0
Note: the
Page | 9