Whirlpool 30" (76.2 cm) Cooktop 설치 및 사용 설명서 - 페이지 5

{카테고리_이름} Whirlpool 30" (76.2 cm) Cooktop에 대한 설치 및 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Whirlpool 30" (76.2 cm) Cooktop 24 페이지. 30" (76.2 cm) wall-mount canopy range hood
Whirlpool 30" (76.2 cm) Cooktop에 대해서도 마찬가지입니다: 사용 및 관리 매뉴얼 (16 페이지), 매뉴얼 (28 페이지)

Whirlpool 30
Cabinet Dimensions
24" (61.0 cm) or
30" (76.2 cm) or
36" (91.4 cm) min.
cabinet opening width
24" (61 cm) min.
30" (76.2 cm)
suggested max.
bottom of cabinet
to cooking surface
18" (45.7 cm)
min. clearance
upper cabinet
to countertop
36" (91.4 cm)
base cabinet
height

Venting Requirements

(Vented Models Only)
Vent system must terminate to the outdoors, except for non-
vented (recirculating) installations.
Do not terminate the vent system in an attic or other enclosed
area.
Do not use a 4" (10.2 cm) laundry-type wall cap.
Use a 6" (15.2 cm) or a 3 " x 10" (8.3 x 25.4 cm) round metal
vent. Rigid metal vent is recommended. Plastic or metal foil
vent is not recommended.
The length of vent system and number of elbows should be
kept to a minimum to provide efficient performance.
For the most efficient and quiet operation:
Use no more than three 90° elbows.
Make sure there is a minimum of 24" (61 cm) of straight vent
between the elbows if more than 1 elbow is used.
Do not install 2 elbows together.
Use clamps to seal all joints in the vent system.
The vent system must have a damper. If roof or wall cap has a
damper, do not use damper supplied with the range hood.
Use caulking to seal exterior wall or roof opening around the
cap.
70
"
(178.6 cm)
min.
76
"
13" (33 cm)
(193.8 cm)
cabinet depth
max.
to bottom of
cabinet frame
Cold weather installations
An additional back draft damper should be installed to minimize
backward cold air flow and a thermal break should be installed to
minimize conduction of outside temperatures as part of the vent
system. The damper should be on the cold air side of the thermal
break.
The break should be as close as possible to where the vent
system enters the heated portion of the house.
Makeup air
Local building codes may require the use of make up air systems
when using ventilation systems greater than specified CFM of air
movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in your
area.
Venting Methods
Vent system can terminate either through the roof or wall. Use
3 " x 10" (8.3 x 25.4 cm) with a maximum recommended vent
length of 35 ft (10.7 m) or 6" (15.2 cm) round vent with a
maximum length of 50 ft (15.2 m) for vent system.
NOTE: Flexible vent is not recommended. Flexible vent creates
back pressure and air turbulence that gently reduces
performance.
Roof Venting
A
D
B
C
A. 6" (15.2 cm) round vent or a
3 " x 10" (8.3 x 25.4 cm) vent
through roof
B. Round vent: use 6" (15.2 cm)
round damper
(purchased separately)
C. 24" (61 cm) to 30" (76.2 cm)
above cooking surface
D. Roof cap
Wall Venting
A
B
D
C
A. 6" (15.2 cm) round vent or a
3 " x 10" (8.3 x 25.4 cm) vent
through the wall
B. 3 " x 10" (8.3 x 25.4 cm) vent
through the wall
C. 24" (61 cm) to 30" (76.2 cm)
above cooking surface
D. Wall cap
5