Terminals
I/P terminal
I/P terminal
O/P terminal
O/P terminal
Battery
I/P Rating
Enclosure Heat
Resistance
For Testing, Commissioning and Simulation purposes, the Condensed Aerosol Generator is
disconnected from the fire protection module FPC-5V2 and replaced by an indication circuit
as per below diagram. The indication circuit includes a resistor and an LED (the indication
circuit must be installed as illustrated below since the LEDs feature polarity).
Bimetallic
Sensor
+
-
FPC-5V2
J7
Linear Heat Detector cable max 10m length
J7
Linear Heat Detector cable max 10m length
J6
Condensed Aerosol Generator 1
J6
Condensed Aerosol Generator 1
Withstands for a short period heat of up to 180
Table1: Specifications
165Ω to 180Ω
+
-
165Ω to 180Ω
+
LED 1
-
Figure 16: Typical connection of the simulation LED
Description
3Vdc Lithium battery (CR2 (3V))
IP30
degrees
Linear Heat
Detector Cable
3.3Vdc
165Ω to 180Ω
LED
0Vdc
+
LED 1
-