Cabling Requirements
3.4
When constructing extension leads the supplied Deutsch Plugs must be used to ensure water-proof
connections are made throughout the installation.
1. Cut cable to required length and strip outer insulation to approximately 25-30mm.
2. Strip inner insulation to approximately 6mm and using a Deutsch Crimping tool, fix pins to the
exposed ends of the cable, including the earth where applicable.
3. Place heat shrink over the end of the cable.
Identify correct socket on plug by the
numbers/letter on the side of the plug and
push through the gasket at the bottom of the
plug until a click is heard and the pin is locked
place.
4. Place the locking mechanism inside the plug to ensure pins remain secure. (Male plugs; locking
mechanism is orange. Female plugs; locking mechanism is green).
5. Using the heat shrink, seal the back of the plug.
Cables are colour coded for easy identification.
When installing system, cables should be only
connected to the correctly coded cable. Colour
Coding for cables is as follows:
Installation
4
FirePro generators must remain disconnected until system is completed and fire control panel is no
longer in a fault or alarm condition. The FirePro Universal Test Lamp (P/N FP-08800) can be used
to take the panel out of a fault condition.
Note: Any required extension leads must be constructed as per the instructions in 3.4 Cabling
Requirements.
1. Connect one of the installed control panels to the "FIRE PANEL 1" plug. This panel will report
faults on the module's siren output, so should installed in a central location with easy access for
any operators of the vessel.
2. Connect all other installed control panels to the other available inputs to the module. Any inputs
that are not used MUST be sealed using a Deutsch plug and heatshrink.
Colour
Circuit
Red
Power Supply
Yellow 1
Activation
Yellow 2
Activation Delayed
Green 1
Detection 1
Green 2
Detection 2
Orange
Siren/Strobe
White
Relay Output
in
Page | 3