Wiring Diagram
5
Programming
6
Programming Module Version 1 - 2.1
6.1
When using a discharge delay module, the FP-08450/08451 Fire Control Panel
must be programmed for extended discharge. (See FP-08450 or FP-08451 Manual)
The Delay Timer Switch allows for the activation of the
connected FirePro generators to be delayed for a period
of up to 240 seconds after the FIP has entered an alarm
condition. Individual programming of modules must
not exceed 4.5 minutes (the total time power is applied
to the activation circuit).
Mode
DELAY Set to
2 second
DELAY Set to
90 seconds
Note: The settings of the module should be recorded in the service logbook and marked in
the space provided on the front of the module.
Delay Timer Switch
Switch 1 – ON
Switch 2 – ON
Switch 1 – OFF
Switch 2 – ON
Mode
Delay Timer Switch
DELAY Set to
150 seconds
DELAY Set to
240 seconds
Switch 1 – ON
Switch 2 – OFF
Switch 1 – OFF
Switch 2 – OFF