FirePro FP-08944-4 빠른 시작 매뉴얼 - 페이지 2

{카테고리_이름} FirePro FP-08944-4에 대한 빠른 시작 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. FirePro FP-08944-4 8 페이지. Combined siren output module, fire system with multiple control panels

FirePro FP-08944-4 빠른 시작 매뉴얼

Introduction

1
General Information
1.1
The FirePro Combined Siren module allows for up to 4 FP-08450/08451 Control Panels to monitor
and operate a singular siren circuit. This module is for use in installations where multiple control
panels have been installed, but individual sirens per panel are not required.

Components List

2
FP-08944-2
FP-08944-4

Design Considerations

3
Operation
3.1
When any of the connected control panels enter an alarm condition, the siren/strobe connected to
the module will operate. Once initiated, the siren/strobe will continue to operate until the control
panel in alarm is silenced, by pressing the mode switch (see FP-08450 Product Manual).
If multiple control panels are in alarm, the siren/strobe will continue to operate until all effected
control panels are silenced.
Fault Monitoring
3.2
The siren/strobe output is a monitored circuit. The supplied end-of-line diode (1N4004) must be
installed on the last siren/strobe in the circuit, otherwise the fire control panel will display a fault.
The FirePro Combined Siren module reports the status of the siren/strobe circuit to the control panel
connected to the "FIRE PANEL 1" input. All other connected control panels are monitored only to
their connection to the module.
Mounting
3.3
For correct installation, the Module must be mounted by four bolts or screws through the mounting
holes in the flange. No penetrations are to be made through the casing of the panel.
The Module enclosure is rated IP65.
Combined Siren Output Module
Fire System with Multiple Control Panels
2 Panels->1 Siren Circuit
Combined Siren Module
Multiple input siren
4 Panels->1 Siren Circuit
Combined Siren Module
Multiple input siren
Model FP-08944
2x DP-3300
Deutsch Plug 3 Pin M/F, c/w hshrink
1x
EOL Diode 1N4004 (Siren/Strobe)
5x DP-3300
Deutsch Plug 3 Pin M/F, c/w hshrink
1x
EOL Diode 1N4004 (Siren/Strobe)
Rev 2.0
Page | 2