Max Heat SP
Sets the maximum heating setpoint value.
Will not ramp or accept setpoints higher that this maximum.
Min Cool SP
Sets the minimum cooling setpoint value.
Will not ramp or accept setpoints lower than this minimum.
Minimum Run Time (MRT)
Sets the minimum run time before a heating/cooling cycle can turn off.
Sets heating/cooling cycle time. Prevents rapid cycling.
Minimum Off Time (MOT)
Sets the minimum off time before another heating/cooling cycle can begin.
Provides compressor short cycle protection.
Fan Cycler
The fan cycler function cycles the HVAC system fan for an ON period followed by an Off
period continuously. Used to provide minimum air ventilation requirements.
When the Fan ON time is set to a value greater than 0, an additional "Cycler" FAN mode is
present when pressing the FAN button.
Fan ON Time
Fan OFF Time
Remote Sensors
RS1 Type
RS2 Type
RS2 Location
Restore Defaults
Restores all settings to factory defaults.
Press Yes to restore defaults,
Press No to exit and not restore defaults
DCN: 2012-11-222-1
Range: 40F to 109F (4C-43C)
Range: 44F to 113F (6C-45C)
Range: 1- 9 Minutes
Range: 5-9 Minutes
Range: 0-120 minutes
Range: 10-120 minutes
Submenu Sensor Setup
A curve, Type 2, Type 3
Range: A curve, Type 2, Type 3
Range: IN (indoors), OUT (outdoors)
Range: Yes, No
Default: 90F (32C)
Default: 60F (15C)
Default: 3
Default: 5
Default: 0 (=OFF)
Default: 10
Default: Type 3
Default: Type 3
Default: IN
Default: No