FIREtec FTEN1 빠른 사용 설명서 - 페이지 4
{카테고리_이름} FIREtec FTEN1에 대한 빠른 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. FIREtec FTEN1 10 페이지. 1, 2 & 4 zone fire detection and alarm control panels
Key:
D = Detector
TYPICAL PANEL WIRING
C = Call-point
S = Sounder
TYPICAL ALARM WIRING
AL2 WIRED AS AL1
S
S
S
END OF LINE RESISTOR
ON LAST SOUNDER
REMOTE INDICATOR
AUX
FLT 1
FLT 2
24V
O/P
F5 250mA(T)
F6 6.3A(T)
+
BATT
TF
AC
MAINS
CABLE ENTRY
CABLE CLAMP
250Va.c 1A(T)
L
20*5mm FUSE
N
END OF LINE COMPONENT
NO SPURS ALLOWED
ON LAST DETECTOR
Zone +Ve
RED
D
D
Zone -Ve
BLACK
EOL COMPONENT
ON ANY UNUSED ZONE
C
D
AUX 1
AUX 2
AL1
AL 2
ZN 1 ZN 2 ZN 3 ZN 4
+
+
+
+
+
+
1A
1A
(T)
(T)
F4
F3
CONTROL PCB
-
EARTH
BATTERY
FUSE F6 = BATTERY SUPPLY (6.3A)
FUSE F5 = AUXILLIARY OUTPUT (250mA)
FUSE F4 = ALARM CIRCIUT 1 (1A)
FUSE F3 = ALARM CIRCUIT 2 (1A)
DETECTOR AND CALL POINT CONNECTIONS
DETECTOR AND CALL POINT CONNECTIONS
REMOTE INDICATOR
(IF FITTED)
IN+
L1 IN
-R
DIODE
To zone circuit
L2
L1 OUT
IN-
SOUNDER AND BELL CONNECTIONS
DETECTOR BASE
IN-
COM
OUT-
IN+
470 Ohms
OUT+
CALL POINT
INSTALLATION PROCEDURE (continued)
D) Connect the cables from the zones (detectors)
and alarms (sounders) to the pcb as shown in
diagrams, ensuring that there are NO spurs from
the main circuit. Fit the end-of-line component
onto the last detector or call-point of each zone
circuit. The end-of-line resistor used on the alarm
circuit can be connected either way round. For
any unused circuits, leave the end-of-line
component / resistor in the terminal block
located on the pcb.
E) The panel has several optional inputs and
outputs.
SOUNDER AND BELL CONNECTIONS
To sounder circuit
OUT+
OUT-
2ND
COM
1ST
SND
SND
SOUNDER
To zone circuit
- -
- -
+ +
+ +
IN-
To sounder circuit
IN+
BELL
•
AUX 1 & 2 -Are volt free relay contacts which
change over when the alarm sounds –Used for
switching auxiliary equipment.
•
AUX 24V - a 24v DC power supply used to power
auxiliary equipment.
•
CLASS CHANGE - wire a switch between COM and
CC terminals to make the sounders operate.
•
PULSE ALERT - wire a switch to terminals BA and
COM to make the sounders pulse.
•
FAULT - Volt free changeover relay contacts that
duplicates the common fault indicator. Used to
drive a remote fault indicator.
OUT+
To sounder circuit
OUT-