Modbuskonfigurering.
MODBUS-INSTÄLLNINGAR
(DIP-switch: 0 = OFF / 1 = ON)
Modbus ID
DIP-switch
1,2,3,4,5 och 6
1
000000
2
100000
3
010000
4
110000
5
001000
6
101000
7
011000
8
111000
9
000100
10
100100
11
010100
12
110100
13
001100
14
101100
15
011100
16
111100
17
000010
18
100010
19
010010
20
110010
Modbus Parity
DIP-switch 7 och 8
None (2 stop bits)
00
None (1 stop bit)
11
Even (1 stop bit)
10
Odd (1 stop bit)
01
Modbus Baud rate
DIP-switch 9 och 10
9600
00
19200
10
38400
01
57600
11
7
TERMINERING
Jumper 1 ON
120 Ohm Termination
DISCRETE INPUTS
Discrete
Function
Inputs(1x)
1x0001
Detector mounted
1x0002
Service alarm
1x0003
Smoke alarm
1x0004
Relay status
HOLDING REGISTER
Holding
Function
reg. (4x)
4x0001
Alarm reset
4x0002
Alarm reset code
4x0003
Manual activate
relay
4x0004
Manual activate
relay code

Modbus configuration.

Value range
Read/
Write
0 or 1
R
0 or 1
R
0 or 1
R
0 or 1
R
Value range
Read/
Write
0 or 234
R/W
234
R
0 or 567
R/W
567
R