Firetrace® Installation Instructions.
Cylinder
When installing the Firetrace® system it is important that a suitable cylinder location is
selected and that the cylinder is orientated correctly.
The cylinder location shall be in a clean area away from direct heat. The cylinder
must not be placed in a location where the ambient temperature is above 80 Degrees
centigrade.
The cylinder shall be readily accessible to allow future servicing / inspections and as close as
practicable to the risk area.
The cylinder shall be adequately fixed to a suitable load bearing surface.
Wherever possible the cylinder shall be mounted vertically and in exceptional circumstances
the cylinder can positioned at an angle of no more than 80 Degrees from vertical.
for clarity)
It is recommended wherever possible that Firetrace® cylinders be mounted vertically.
Where vertical locating is not possible the systems can be mounted within 80° of
As indicated in the above drawing when cylinders are fitted at an angle the
THIS FIRETRACE® SYSTEM IS SUITABLE FOR HORIZONTAL
Cylinder Gauge
80° Max
.
vertical
gauge must face uppermost.
MOUNTING.
(see cylinder label
X