Press "Motor Rotation"
Press the "Start" button to start the electric motor and validate that the electric motor is rotating in the correct
direction. If it is not rotating in the correct direction adjust the motor connections as per below. Press the "Stop"
button to stop the electric motor.
Acknowledge that the motor is turning in the right direction by checking the Check on Normal Power selector box.
Once the motor rotation has been checked, go back to the controller start-up page and press the "Verify pressure"
button.
WARNING!
On a Wye-Delta closed transition starter, if the transition from Wye to Delta occurs (after 5 to 8 seconds depending
on the motor HP), the manual stop push button will be disabled for 80 seconds. To stop the engine before the end of
the 80 second delay, use the disconnecting means handle.