Point check function
Press the LED DISPLAY button( Mute button for some
remote controllers) of remote controller three times and then
press AIR DIRECTION button ( Swing button for some
remote controllers) three times within 10 seconds, the buzzer
ring last 2 seconds,the air conditioner will enter the information
enquiry status. After that, press the LED DISPLAY button to
enquiry the next one information and press the
DIRECTION button to enquiry the last one information. When
the air conditioner enter the information enquiry status, it will
display the code name in 2 seconds, the details are as follows:
Enquiry information
Displaying code
T1
T1
T2
T2
T3
T3
T4
T4
T2B
Tb
TP
TP
TH
TH
Targeted Frequency
FT
Actual Frequency
Fr
Indoor fan speed
IF
Outdoor fan speed
OF
EXV opening angle
LA
Compressor continuous
CT
running time
Causes of compressor stop
ST
Reserve
A0
Reserve
A1
Reserve
b0
b1
Reserve
b2
Reserve
b3
Reserve
b4
Reserve
b5
Reserve
Reserve
b6
Reserve
dL
Reserve
Ac
Uo
Reserve
Td
Reserve
14
AIR
Meaning
T1 temp.
T2 temp.
T3 temp.
T4 temp.
T2B temp.
TP temp.
TH temp.
Targeted Frequency
Actual Frequency
Indoor fan speed
Outdoor fan speed
EXV opening angle
Compressor continuous
running time
Causes of compressor stop
When the air condtioner enter the information enquiry
status, it will display the code value in the next 25s after
display name is displayed, the details are as follows,
Display
Enquiry
Meaning
value
information
-1F,-1E,
T1,T2,T3,
-25,-24,-23,-22,
T4,T2B,TP,
-1d,-1c,
-21,-20
-1b,-1A
TH,
-19-99
-19-99
Targeted
Frequency,
A0,A1...A9 100,101......109
Actual
b0,b1...b9
110,111....119
Frequency
c0,c1....c9
120,121....129
d0,d1...d9
130,131....139
E0,E1...E9
140,141....149
F0,F1...F9
150,151....159
OFF
Indoor fan
0
speed/
Low speed,
1,2,3,4
Outdoor
Medium speed,
fan speed
High speed,
Turbo
Actual fan speed
14-FF
=Display value
turns to decimal
value and then
multiply 10. The
unit is RPM.
Actual EXV
0-FF
EXV
opening value=
opening
Display value
angle
turns to decimal
value and then
multiply 2.
Compressor
0-255 minutes
continuous
0-FF
running
time
For the detailed
Causes of
0-99
meaning, please
compressor
consult with
stop.
engineer
Reserve
0-FF
Reserve
0-FF
0-FF
Reserve
0-FF
Reserve
Reserve
0-FF
15
Remark
1. All the displaying
temperature is actual
value.
O
2. All the temperature is C
no matter what kind of
remote controller is used.
3. T1,T2,T3,T4,T2B display
range:-25~70, TP display
range:-20~130.
4. Frequency display range:
0~159HZ.
5. If the actual value
exceeds the range, it will
display the maximum
value or minimum value.
For some big capacity
motors.
For some small capacity
motors, display value is
from 14-FF(hexadecimal),
the corresponding fan
speed range is from
200-2550RPM.
If the actual value exceeds
the range, it will display the
maximum value or minimum
value.
Decimal display