CALEFFI QuickSetter+ 132635AFC 매뉴얼 - 페이지 4
{카테고리_이름} CALEFFI QuickSetter+ 132635AFC에 대한 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. CALEFFI QuickSetter+ 132635AFC 12 페이지. Balancing valve with flow meter
Installation
132 series
5D
132 series
Pump
10D
7
6
5
4
3
2
The balancing valves, with built-in flow meter, must be installed by
qualified technical personnel in accordance with the instructions given in
this manual and with current regulations.
Clean the pipes of any debris, rust, welding slag and any other
contaminants.
As in all piping circuits it is important to pay attention to the cleanliness
7
6
7
5
6
of the entire system.
4
5
3
4
2
3
2
For optimal operation, any air in the water must be removed.
In order to ensure measuring accuracy, the balancing valves with flow
meter must be installed by keeping a straight section above them at least
as long as five diameters, increased to at least ten diameters if the nearest
device upstream is a pump.
The valves must be installed so that:
- the direction of the flow agrees with that of the arrow on the
valve body.
- there is easy access to the flow meter valve, control stem and dial
with the calibration adjustment range.
The valves can be fitted on either vertical or horizontal pipes.
7
6
5
4
3
2
Do not install in direct sunlight.
4