SATK20 & SATK30
Operating Cycles SATK20 Low and Medium Temperature
Domestic water generation: DHW preheating function
The domestic water preheating function is signalled by the
flashing yellow DHW LED.
This function is less of a priority than any domestic water or
heating cycles.
Heating cycle
Modulating temperature regulation with compensated set
point SATK20103 - LOW temperature
The function is enabled by setting dip switch 1 to the OFF
position.
When the function is enabled, the flow temperature is modified
according to the temperature detected by the compensation
probe.
This keeps the actual thermal output of the under floor heating
and therefore the ambient thermal load under control. The
thermal response time of the system is thus minimised.
Safety and alarms
Error codes associated with faults signalled by the lighting up of
the FAULT LED are also shown on the display (see page 8).
Components - SATK20303 HIGH Temperature HIU
Item Component
1
Frame
2
Electronic controller
3
Heat ON/OFF valve
4
DHW production modulating valve
5
Drain cock
6
DHW temperature probe
7
DHW heat exchanger
8
DHW priority flow meter
9
Heat meter spool piece
10
Air vent cock
11
System strainer/heat meter flow probe pocket
12
Primary circuit isolating valve
Functional characteristics
Max. heating temp.
ON/OFF regulation:
85˚C
Set point regulation
DHW production range: 42 to 60˚C
Optional functions
Domestic water cycle:
domestic water preheating function
Operating Cycles SATK20
1
OFF
60
4
1
2
3
4
5
Factory settings
6
5
4
4
3
2
1
11
ON
12
11
10
9
8
7
6