Technical Description

Principle of operation

The RER 133 Bus Connection Module is designed to work with RE_ 54_ products.
The module utilizes the RS-232 communication port located on the rear panel of the
RE_ 54_. The module is not designed to be connected to any other ABB product,
nor to any third party products.
REF 542 and REF 542plus are not supported by RER 133.
The signal levels and the functionality of the RER 133 module are defined in the
RS-485 standard. RER 133 module is a regular type of RS-485 interface, meaning
that a maximum of 32 nodes can be connected in a daisy chain type of bus
configuration.
Collision detection on the RS-485 bus is supported when a maximum of 32 nodes
are connected to the same daisy chain. In order for collision detection to operate, the
communication speed has to be set to 4800, 9600 or 19200 bits/s. These speeds are
set by using the DIP switches on the front of the module. For an example on how to
set these DIP switches, please see section "Module configuration" on page 9. When
collision detection is not used, the communication speed does not have to be set.
Fig. 4.-1 Daisy chain