Caleffi solar iSolar Wmz-G1 매뉴얼 - 페이지 7

{카테고리_이름} Caleffi solar iSolar Wmz-G1에 대한 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Caleffi solar iSolar Wmz-G1 16 페이지.

2.2 Menu structure

Main Menu
1.

Measured values

2.
Reports
3.

Balance values

4.
Adjust. values
The clear text display shows a 4-line extract of the se-
lected menu.

2.3 Initial commissioning

Adj. values:
language
Date
Time
• Language:
Î Select the menu item "Language" with button 1 and
confirm with button 3
Î Select the desired language with buttons 1 and 2
Î In order to confirm the selection, briefly press button 3
and answer the security inquiry with "Yes"
Î In order to change to the adjustment values menu, select
the menu item "back" and confirm with button 3
The following languages are available: German ("Deutsch"),
English, Spanish ("Castellano"), French ("Français"), Italian
("Italiano"). The factory setting is "English".

2.4 Operating control lamp

3. Measured values
S1:
T1: 74.8 ° c
P 1: 0.14 bar
P: 9 W
Note:
"Power" and "Heat" are only indicated when
at least one of the sensors connected is a VFS
type sensor and the option "Heatmeter" in the
submenu "Adj. values" has previously been set
to "Yes".
english
01.01.2009
00:00
S2:
T2: 23.9 ° C
Q2: 5.55 l/min
Heat: 19944 Wh
In the first line of each submenu you will find the option
"back" (except in submenu "measured values"), by means of
which you can return to the former display level.
After a short time of operation, the display switches to the
submenu "measured values" which is then indicated during
normal operation.
Î Establish the power supply
In the "Adjust. Values" menu, carry out the adjustments
mentioned below. For further information on the adjustment
values, see chap. 5.
• Date:
Î Select the menu item "Date" with button 1 and confirm
with button 3
Î Adjust the year, the month and the day with buttons 1
and 2 and confirm each with button 3
Î In order to confirm the adjustment, briefly press button
3 and answer the security inquiry with "Yes"
• Time:
Î Select the menu item "Time" with button 1 and confirm
with button 3
Î Adjust the hours and the minutes with buttons 1 and 2
and confirm each with button 3
Î In order to confirm the adjustment, briefly press button
3 and answer the security inquiry with "Yes"
The device is equipped with a red/green operating control
lamp. The following operating states can be visualized:
green constant
normal operation;
green flashing
measured value outside alarm limit
red flashing
defective sensor
not illumated
no voltage
In the submenu "Measured values", different measurement
val ues are shown: the measured values depend on the sen-
sor type and can be the following:
Sensor 1:
T1 (temperature in ° C or ° F)
p1 (pressure in bar)
Q2 (flow rate in l/min, m³/h or gallon/h)
P (in W) – values over 999,999 W cannot be
processed. In such a case, both the displayed
value and the VBus
at 999,999 W.
Sensor 2:
T2 (temperature in °C or ° F)
p2 (pressure in bar)
Q2 (flow rate in l/min, m³/h or gallon/h)
Heat (in
Wh, kWh, MWh, kJ, MJ or
S1 measures the flow temperature, S2 the return
temperature.
If the flow temperature is lower than the return temperature,
heat quantity measurement is not carried out. In that case,
the power is displayed as 0.
Briefly press button 3 in order to get back to the main menu.
data packet value remain
®
GJ.)
7
|