eControls Comfort365 C365T11 설치 프로그램 및 사용자 설명서 - 페이지 8

{카테고리_이름} eControls Comfort365 C365T11에 대한 설치 프로그램 및 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. eControls Comfort365 C365T11 13 페이지.
eControls Comfort365 C365T11에 대해서도 마찬가지입니다: 사용자 설명서 (4 페이지), 설치 프로그램 및 사용자 설명서 (13 페이지), 사용자 설명서 (4 페이지), 설치 프로그램 및 사용자 설명서 (13 페이지), 설치 프로그램 및 사용자 설명서 (13 페이지), 설치 (2 페이지)

eControls Comfort365 C365T11 설치 프로그램 및 사용자 설명서
18 USER (Manual) Airflow Control Enabled
Factory Default: On. Range: On or Off.
ore
Manual airflow control enables the homeowner
ption
to direct more airflow to the living or sleeping
le,
space as they desire. This option is ideal for
homeowners who have an unusual work
er.
schedule, home office or spend more time in one
space than the other. The User Menu is used to
turn off automatic airflow control. Nighttime
Airflow option is still enabled but can be turned
off using the User Options.
Use the
DOWN
key
to select OFF only if
disabling manual
airflow control. (Not
typical)
Touch NEXT or ENTER.
19 Upstaging Time
Factory Default: 10 min. Range: 5 to 30 min.
Use the
UP/DOWN
keys to set the time at
which second stage
heating or cooling is
activated.
Touch NEXT or ENTER.
For options 20 - 23, use the installer test
o
n the following page to determine the
max
imum allowable airflow.
20 Maximum Airflow in Heating to Sleeping Area
Factory Default: 160%. Range: 100% to 160%.
Use the
UP/DOWN
keys to select the
maximum allowable
airflow in heating to
the sleeping area.
Touch NEXT or ENTER.
21 Maximum Airflow in Cooling to the Sleeping Area
Factory Default: 150%. Range: 100% to 160%.
Use the
UP/DOWN
keys to select the
maximum allowable
airflow in cooling to
the sleeping area.
Touch NEXT or ENTER.
22 Maximum Airflow in Heating to the Living Area
Factory Default: 160%. Range: 100% to 160%.
Use the
UP/DOWN
keys to select the
maximum allowable
airflow in heating to
the living area.
Touch NEXT or ENTER.

INSTALLER SECTION

23 Maximum Airflow in Cooling to the Living Area
Factory Default: 150%. Range: 100% to 160%.
Use the
keys to select the
maximum allowable
airflow in cooling to
the living area.
Touch NEXT or ENTER.
24 Maximum Temperature Differential
Option
Factory Default: 2 F.
This is the maximum allowable temperature
difference between the sleeping and living area
temperatures. When the temperature difference is
NEXT
ENTER
equal to or greater than the allowed differential,
the airflow is adjusted.
Use the
keys to select the
maximum allowable
temperature
Option
difference between
the sleeping and
living area.
NEXT
ENTER
Touch NEXT or ENTER.
25 Factory Restore
WARNING! Factory Restore resets ALL settings.
To exit this option,
touch
ENTER, or the hidden
Back key.
Sleeping
Option
Heat
Airflow %
To restore factory
settings, touch the
UP
key to display
NEXT
ENTER
YES then touch
ENTER.
Sleeping
Option
Airflow %
Cool
NEXT
ENTER
Option
Heat
Airflow %
Living
NEXT
ENTER
UP/DOWN
Option
Airflow %
Living
NEXT
o
o
o
Range: 0 to 10 F
UP/DOWN
Option
NEXT
Option
NEXT
or
NEXT
Option
NEXT
Page 8 of 12
Cool
ENTER
ENTER
ENTER
ENTER