ABB OVRHSP 6003Y Series 설치, 운영 및 유지보수 매뉴얼 - 페이지 8
{카테고리_이름} ABB OVRHSP 6003Y Series에 대한 설치, 운영 및 유지보수 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. ABB OVRHSP 6003Y Series 12 페이지. Surge protective devices
Conduit openings (OVRHSP)
If desired, punch holes at this time for the conduit or nipple or wait until the OVRHSP unit is mounted to the building structure.
Punch holes only in the designated areas as shown in the following illustration.
CAUTION:
Careful consideration must be made when selecting an area for conduit entry. There are several components inside the
enclosure that may interfere with the conduit entry path, therefore, ensure the path is clear of all objects before drilling.
Damages caused by installation errors are not covered under the product warranty.
See Figures 6A and 6B for conduit openings and enclosure dimensions.
Figure 6A
Conduit Openings and Enclosure Mounting Dimensions
(OVRHSP)
19.05 (3/4)
Myers Hub
(W1)
(W2)
(D1) (D2)
(H1)
OVRHSP 60–100
Dimensional specifications
Dim
OVRHSP 60, 80, 100
H1
152.4 (6.00)
H2
171.5 (6.75)
H3
190.5 (7.50)
W1
152.4 (6.00)
W2
101.6 (4.00)
D
–
D1
105.7 (4.16)
D2
50.8 (2.00)
Weight
4.5 kg (10 lbs.)
All measurements in millimeters (inches) and kg (pounds)
8 Product manual | OVRHSP/OVRHSR surge protective device
(D)
ø7.87 (0.31)
(H2)
(H3)
Allowable area for conduit entry
OVRHSP 120–160
(W1)
(W2)
ø7.87 (0.31)
(H1)
(H2)
(H3)
OVRHSP 120, 160
254.0 (10.00)
273.1 (10.75)
292.1 (11.50)
203.2 (8.00)
152.4 (6.00)
157.5 (6.20)
–
–
9 kg (20 lbs.)
(D)
(W1)
(W2)
Allowable area for conduit entry
OVRHSP 200–400
OVRHSP 200, 240, 300, 400
355.6 (14.00)
374.7 (14.75)
393.7 (15.50)
304.8 (12.00)
254.0 (10.00)
157.5 (6.20)
–
–
18 kg (40 lbs.)
ø0.31 (7.87)
(H1)
(H2)
(H3)