Aerco AM 1000W 애플리케이션 매뉴얼 - 페이지 9
{카테고리_이름} Aerco AM 1000W에 대한 애플리케이션 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Aerco AM 1000W 20 페이지. Gas-fired boilers and water heaters venting application
Aerco AM 1000W에 대해서도 마찬가지입니다: 애플리케이션 매뉴얼 (8 페이지)
Figure 3: Combustion Air Roof Termination Locations
All inlet air ducts must be sealed air tight.
•
•
When using sealed combustion, the combustion air inlet and vent outlet must be located on
the same surface (same wall, roof, etc.). See Figures 4. This is required so that equal pressure
zones are acting on both the air inlet and vent outlet. This makes the installation a balanced
vent system, which helps maintain stable combustion characteristics.
Figure 4: Sealed Combustion Air Inlet and Vent Outlet Locations (Wall & Roof)
PR1 04/08/2014
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
AM Series Venting
Application Guide
GF-146
GF-146-V
TAG-0075_0B
TAG-0075_0B
Page 9 of 20