Armstrong DRV40 설치 및 운영 매뉴얼 - 페이지 15
{카테고리_이름} Armstrong DRV40에 대한 설치 및 운영 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Armstrong DRV40 16 페이지. Modbus networking
Armstrong DRV40에 대해서도 마찬가지입니다: 문제 해결 매뉴얼 (5 페이지)
Enumeration Details
Enumeration 1 - Valve Status
0 = OFF - R/W
1 = ON - R/W
2 = FULL COLD - R/W
6 = DISINFECTION - RO
7 = ERROR - RO
Enumeration 2 - Valve Error Codes
0 = NO ERROR
1 = OVER TEMPERATURE
2 = STUCK MOTOR
3 = MOTOR CALIBRATION
4 = VALVE FAILURE
5 = THERMISTOR FAILURE
6 = UNCONFIGURED
7 = A TO D ERROR
8 = RAM ERROR
9 = EE ERROR
10 = FLASH ERROR
11 = ALGORITHM ERROR
12 = CONTROLLER ERROR
13 = BATTERY ERROR
14 = SCHEDULER ERROR
The DRV Programming Sequence
Set Reg 4 to OFF before adjusting any of the following registers:
Reg 400-411
Set Reg 4 back to ON
All other registers can be set without setting Reg 4 to OFF.
IMPORTANT!
The disinfection feature has a specific sequence as all Alerts and Errors are disabled temporarily while hot water
is flushed through the DRV. Please read the following section on setting up the disinfection sequence carefully.
The DRV 25/40/80's disinfection feature is a manual process and for safety reasons must be monitored constantly.
Armstrong International
IOM-776
Brain
®
Modbus Networking