Enumeration Details

Enumeration 1 - Valve Status
0 = OFF - R/W
1 = ON - R/W
2 = FULL COLD - R/W
6 = DISINFECTION - RO
7 = ERROR - RO
Enumeration 2 - Valve Error Codes
0 = NO ERROR
1 = OVER TEMPERATURE
2 = STUCK MOTOR
3 = MOTOR CALIBRATION
4 = VALVE FAILURE
5 = THERMISTOR FAILURE
6 = UNCONFIGURED
7 = A TO D ERROR
8 = RAM ERROR
9 = EE ERROR
10 = FLASH ERROR
11 = ALGORITHM ERROR
12 = CONTROLLER ERROR
13 = BATTERY ERROR
14 = SCHEDULER ERROR
The DRV Programming Sequence
Set Reg 4 to OFF before adjusting any of the following registers:
Reg 400-411
Set Reg 4 back to ON
All other registers can be set without setting Reg 4 to OFF.
IMPORTANT!
The disinfection feature has a specific sequence as all Alerts and Errors are disabled temporarily while hot water
is flushed through the DRV. Please read the following section on setting up the disinfection sequence carefully.
The DRV 25/40/80's disinfection feature is a manual process and for safety reasons must be monitored constantly.
Armstrong International
IOM-776
Brain
®
Modbus Networking