INSTALLATION AND ADJUSTMENT INSTRUCTIONS
No water heater will work satisfactorily if improperly installed and operated. These instructions contain important
information for the installation and adjustment of the FLO-RITE-TEMP Water Heaters. Read these instructions carefully
before installing this unit. FAILURE TO ADHERE TO THESE INSTRUCTIONS COULD RESULT IN SERIOUS
BODILY INJURY OR PROPERTY DAMAGE.
STEAM PIPING INSTALLATION OF A SINGLE UNIT
Single and Double Wall
NOTE: FLO-RITE TEMP is provided with (1) one Armstrong Steam Trap and Thermostatic Air Vent
(shaded). All other items shown not included.
NOTE: units may be piped in parallel for larger capacity requirements. See Fig. 15-1 for an example of parallel unit
installation.
The unit includes the mixing valve mounted to the heat exchanger, channel iron and U-bolts mounted, thermostatic
air vent installed on the heat exchanger, a water pressure pop off valve integral to the unit control valve and a separate
Armstrong Inverted Bucket Steam Trap.
1.
Install the FLO-RITE-TEMP with adequate room to allow for tube bundle removal when cleaning is required. See
Table 12-1 for specific dimensions.
2.
If 2-15 psig of steam is available a pressure reducing valve is NOT required. If a pressure reducing valve is required,
an Armstrong Inverted Bucket Steam Trap is recommended to drain condensate at the inlet of the pressure reducing
valve.
3.
An Armstrong Y-strainer should be installed before the pressure reducing valve to reduce the chance of dirt
fouling.
FLO-RITE-TEMP
INSTANTANEOUS WATER HEATER
NOTICE
Steam In
Armstrong Pressure
Reducing Valve (if req'd)
Armstrong
TVS Trap
Armstrong Thermostatic
Vacuum
Breaker
STEAM SIDE INSTALLATION
(Refer to Fig. 2-1)
Safety Relief
Valve
Gate
Valve
GP-2000
Pressure
Gauge
Air Vent
2-15 psig Steam
in the Shell
Armstrong
I.B. Trap
Fig. 2-1
2