Aerco SmartPlate SP33 애플리케이션 매뉴얼 - 페이지 11

{카테고리_이름} Aerco SmartPlate SP33에 대한 애플리케이션 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Aerco SmartPlate SP33 15 페이지. Boiler interface

SmartPlate Application Guide for Boiler Interface
The non-AERCO boiler buffer tank sizing program will require the following inputs:
Boiler Model.
Water volume contained in a single boiler.
Quantity of boilers.
Boiler primary loop flow rate.
Boiler maximum supply temperature to SmartPlate.
Boiler Minimum Input.
Boiler Maximum Input.
Boiler Full Fire Efficiency.
Boiler Type. Choices include: condensing firetube, condensing cast aluminum, scotch
marine, all watertube, and all other boilers.
SmartPlate setpoint temperature.
SmartPlate model number.
Quantity of SmartPlates.
Domestic hot water building design load.
Building or Application Type. Choices include: elementary school, high school, hospital,
hotel, laundry, process, office building, prison, residential apartment, restaurant,
university building, and university dorm.
Pipe diameter and length to calculate piping volume.
Minimum flow per boiler - per the manufacturer's recommendation.
The SmartPlate system should be piped as a zone of the heating system utilizing non-AERCO
low mass boilers, as shown in Figure 8, below.
01/08/2016 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
Technical Application Guide
SP-1010
TAG-0026_0B
Page 11 of 15