5.1 Tools

• Insulated tools sized to match nuts, bolts and cables in use
• Voltmeter
• Post cleaner and wire brush
• Personal protective equipment

5.2 Locating and Securing the Battery

Locate the batteries close to the power conversion device in order to minimize the length of the battery cables. Care should
be taken to ensure adequate clearance above the batteries is maintained for access to both battery and power conversion
device connections and disconnects.
AES Battery performance and service life will be optimized when they are operated in an ambient temperature of 15°C to
25°C (59°F to 77°F). Care should be taken to ensure that the battery's temperature is > 0°C (32°F) during charging.
• Battery can be strapped in place with non-conductive nylon straps
• Battery may have hold down brackets at the base of the battery

5.3 Installation

Lithium batteries are very sensitive to voltage and undersized battery cables will impede battery and system performance.
The thickness (cross section) of cable used should exceed the recommended minimum for the charger installation whenever
possible. Do not use or install a battery temperature sensor.
• Confirm that battery is set to OFF
• If the battery circuit has a disconnect - open the disconnect to isolate battery
• Cable connection points should always be kept clean
• Broken, frayed, brittle, kinked or cut cables should never be used
• Secure the new battery - be careful not to ground the terminals to any metal mounting, fixture, or body part
• Connect battery cables - connect the ground cable last to avoid sparking
• Terminals are button-type, M8 female - recommended torque is 9.0 Nm (6.64 ft-lb)
• If the battery circuit has a disconnect - close disconnect to reconnect the battery
• Set the battery to ON
Copper compression lug
Shrink-wrap to
color-code the cable
Terminal surface
Terminal burnout is caused by:
• Discharge currents exceeding allowable limits
• Improper cable installation
• Improper cable sizing
• Improper terminal torque
M8" bolt (supplied with battery)
Lock washer (supplied with battery)
Flat washer (supplied with battery)
Battery cable lug
Ensure nothing is between
the terminal surface and the
battery cable lug
All cable ends must be connected to battery terminals without
any washers between terminal bushings and cable ends.
Without exception, product experiencing terminal burn out
will not be warranted.
▲ NOTE!
▲ NOTE!
Washers ARE NOT
Washers ARE NOT
compressed!
compressed!
Terminal hardware
Terminal hardware
IS bottomed out!
IS bottomed out!
Terminal hardware
Terminal hardware
IS NOT bottomed out!
IS NOT bottomed out!
6