DISCOVER 42-48-6650 운영 매뉴얼 - 페이지 4

{카테고리_이름} DISCOVER 42-48-6650에 대한 운영 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. DISCOVER 42-48-6650 13 페이지. Wall mount bracket for aes battery
DISCOVER 42-48-6650에 대해서도 마찬가지입니다: 설치 매뉴얼 (6 페이지)

Maximum Operating Limits
Continuous Charge Current*
Continuous Discharge Current*
Operating Voltage (Min / Max)
Charge Temperature (Min / Max)
Discharge Temperature (Min / Max)
Storage Temperature (Min / Max)
* Effects of AC Ripple must be taken into consideration when sizing and configuring your system.

2.2 Recommended Battery Operating Limits

Although the battery is capable of performing up to the Maximum Battery Operating Limits noted, the following settings are
recommended to maximize battery health and account for unforeseen external conditions.
Recommended Operating Settings
Max Continuous Charge Current
Max Continuous Discharge Current
Charge Voltage (Bulk/Absorb)
Low Voltage Disconnect
Operating Temperature
Charge Voltage
Nominal Interruption Time - Peak Current Characteristic of Discover BMS
600
500
400
300
200
100
0
150
200
Intentional bypassing of BMS to operate the battery
outside maximum and minimum limits voids warranty.
Charge Voltage (Float)
14-24-2800
12-36-6700
110 Adc
150 Adc
110 Adc
150 Adc
27.2 V
40.8 V
22.4 V / 29.2 V
33.6 V / 43.8 V
0°C / 45°C (32°F / 113°F)
-20°C / 50°C (-4°F / 122°F)
-20°C / 45°C (-4°F / 113°F)
300
250
350
Current (Adc)
Interrupt Time (s)
▲ NOTE!
14-24-2800
12-36-6700
< 78 A
< 106 A
< 78 A
< 106 A
27.2 V
40.8 V
26.8 V
40.2 V
24 V
20°C (68°F)
12-48-6650
130 Adc
130 Adc
54.4 V
44.8 V / 58.4 V
400
12-48-6650
< 92 A
< 92 A
54.4 V
53.6 V
36 V
48 V
4