All other room devices must have their EOL terminations set to OFF.
Figure 8:
Setting the EOL Terminations on the Allure EC-Smart-Air Sensor for ECB-600 or ECL-600 Series controllers
When ECx-4xx IO Extension Modules are installed with an ECB-600 / ECL-600 Series controller and with room device(s):
£
Only the EOL terminations on the last ECx-4xx IO Extension Module and the last room device are set to ON.
£
All other ECx-4xx IO Extension Modules and room devices must have their EOL terminations set to OFF.
Figure 9:
Setting the EOL Terminations when Allure EC-Smart-Air Sensors are used with ECx-4xx IO Extension Modules