Network Access from the Sensor
ON
ORKS
For commissioning and maintenance purposes, the L
available with ECL-PTU series controllers, or the ECL-VAVS).
Setting the two (2) Net to Subnet Port Settings jumpers inside the ECL Series controller to Enable will connect the main L
EC-Smart-Vue sensor subnetwork Cat 5e cable.
Recommendation: Only a limited number of controllers on a L
Subnet Port Settings jumpers enabled. Enabling too many Allure EC-Smart-Vue sensors with network access may
cause network communication issues. If there are any network communication problems, see the Troubleshooting
section in this document.
The Cat 5e cable length is restricted by the maximum allowable subnetwork bus length (see Subnetwork Bus Total Length [pg. 5]). The standard Net to
Subnet Port Settings jumper setting is Disable.
Figure 14:
ECL Series controller: Net to Subnet Port Settings Jumpers
Figure 15:
ECL-VAV Series controller: Net to Subnet Port Settings Jumpers
W
network is optionally available from the Allure EC-Smart-Vue sensor audio plug port (not
ON
ORKS
Net to Subnet
Port Settings
Enable
Disable
Enable
Disable
W
network segment should have their Net to
ON
ORKS
Net to Subnet
Port Settings
W
network to the Allure
ON
ORKS
13 / 16