8.
RJ9 Accessories Wiring
4 bidirectional RJ9 accessory inputs (RS PORT 1, RS PORT 2, RS
PORT 3 and RS PORT 4) are available to connect RJ9 accessories
through a RJ9/RJ9 cable. Refer to the RJ9 accessory's documentation
for more information.
Only one wireless receiver per module. The receiver uses
the first bidirectional RJ9 input (R1) from the module.
9.
Communications Wiring
The recommended cable type for LonWorks
is 22 AWG (0.65 mm), twisted pair, unshielded. The LonWorks
communication wire is polarity insensitive and can be laid out in a
bus, star, loop or free topology. For loop topology, polarity is important,
special care must be taken when connecting the LonWorks network to
avoid a short circuit.
Communication wiring must be connected using the provided
detachable connectors.
It is recommended to use the bus topology network
configuration for all LonWorks communication wiring, as it
allows for easy network troubleshooting.
Connect both wires to the LON1 and LON2 terminals of the module. If
inserting multiple wires in the terminals, ensure to properly twist wires
together prior to inserting them in the terminal connectors.
For more information and detailed explanations on network topology
and wire length restrictions, refer to the Network Guide. It can be
downloaded from our website.
It is important to use proper network terminators depending
on the type of network topology used. Failure to do so
might result in communication errors between modules.
Selecting Network Terminators
For a bus topology, 2 network terminators are required (1 at each end
of the bus topology channel). For a free topology, 1 network terminator
is required and it can be put anywhere on the channel.
LON Network
To next device
The cable length is restricted by the maximum allowable subnetwork
bus length.
10.
Wireless Installation
When connected to a RFR Wireless Receiver, modules can receive
input signals from a wide selection of wireless devices. These devices
are easy to install, and can be mounted on a wide range of building
materials.
The RFR Wireless Receiver is available in 868 MHz frequency. Refer to
the documentation of the RFR Wireless Receiver for more information.
communications
®
Device 1
LON 1
LON 2
Device 2
LON 1
LON 2
Before connecting any wireless equipment to the module,
refer to the Open-to-Wireless™ Solution Guide.
Only one wireless receiver per module. The receiver uses
the first bidirectional RJ9 input (R1) from the module.
Connecting the RFR Wireless Receiver
The RFR Wireless Receiver is connected to the module using a 12 m
RJ9/RJ9 connection cable. Do not exceed this cable length.
Figure 10-1:
RFR Wireless Receiver
11.
Maintenance
Turn off power before any kind of servicing.
Each module requires minimal maintenance, but it is important to take
note of the following:
If it is necessary to clean the outside of the module, use a dry cloth.
Retighten terminal connector screws annually to ensure the wires
remain securely attached (recommended tightening torque 0.5 Nm).
12.
Disposal
The Waste Electrical and Electronic Equipment (WEEE) Directive
sets out regulations for the recycling and disposal of products. The
WEEE2002/96/EG Directive applies to standalone products, for
example, products that can function entirely on their own and are not a
part of another system or piece of equipment.
For this reason Distech Controls products are exempt from the WEEE
Directive. Nevertheless, Distech Controls products are marked with
the WEEE symbol
, indicating modules are not to be thrown away
in municipal waste.
Products must be disposed of at the end of their useful life according
to local regulations and the WEEE Directive.
13.
Complementary Information
This device is designed for type 1 action
This device is designed for type 1.b action
This device presents an A class software
The EMC immunity test has been passed using 230 VAC and 30
mA.
The Ball Pressure Test temperature is 167°F (75°C)
The SELV does not exceed 42 VDC
The maximum accessible voltage is 5 VDC.
All traveling cables permanently installed present a X type anchor.
All cables must be be able to operate above 176°F (80°C)
This product is not repairable. If out of order, it must be returned
to Distech Controls.