SAFETY DEVICES
Photocells
Configure contact CX or CY (NC), safety input for photocells.
See F2 (CXinput) or F3 (CY input) set to:
- C1 reopening during closing. When the gate is closing, opening the contact triggers the inversion of movement until the gate is fully open again;
- C2 closing during opening. When the gate is opening, opening the contact triggers the inversion of movement until the gate is completely closed.
- C3 partial stop. Stopping of the gate, if it is moving, with consequent automatic closing (if the automatic closing function has been entered);
- C4 obstruction wait. Stopping of the gate, if it is moving, which resumes movement once the obstruction is removed.
 If contacts CX and CY are not used they should be deactivated during programming.
RX
DIR
10 11 TS 1 2 3 3P 4 5 7 CX CY
Photocells (safety test)
At each opening and closing command, the control board checks the efficacy of the safety devices (such as, photocells).
Any malfunction inhibits any command and the display will show the Er4 wording.
Enable function F5 in programming.