Camille Bauer SINEAX U553 사용 설명서 - 페이지 11
{카테고리_이름} Camille Bauer SINEAX U553에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Camille Bauer SINEAX U553 12 페이지. Transducer for ac voltage
Camille Bauer SINEAX U553에 대해서도 마찬가지입니다: 사용 설명서 (12 페이지)
Symbol
Meaning
Double insulation, device of protection class 2
Test voltage of insulation according to IEC60051:
3,7
AC 3.7 kV
Class icon to the EN60688:
0,5
error limit 0.5% of span
CE conformity mark. The device fulfi lls the
requirements of the applicable EC directives.
CSA approved for USA and Canada
fi le-nr. 204767
Germanischer Lloyd
Type approval certifi cate: 12 259-98 HH
Caution!
General hazard point.
Read the operating instructions.
General symbol: Input
General symbol: Output
General symbol: Power supply
Measurement category CAT III for current and
CAT III
voltage inputs
6. Adjustable measuring range
Reliably isolate the measuring input from
dangerous voltages.
Setting:
Admissible alteration of full scale
output, variable sensitivity, adjust-
able with potentiometer P200.
Setting range:
0.85 - 1.15 · U
100%
P201
P200
10 11 12 13
+
–
0,5
4-20mA
Fig. 6. Locations of the potentiometers P201 and P200.
(± 15%)
N
U
N
0
0
Input
0.85
1
1.15
7. Commissioning and maintenance
Switch on the power supply and the measuring input. It is
possible during the operation to disconnect the output line
and to connect a check instrument, e.g. for a functional test.
No maintenance is required.
8. Releasing the transducer
Release the transducer from a top-hat rail as shown in
Fig.7.
Fig. 7
9. Instruments admissions
Germanischer Lloyd
Type approval certifi cate: 12 259-98 HH
CSA approved for USA and Canada
fi le-nr. 204767
FCC Compliance and Canadian DOC Statement
This equipment has been tested and found to comply with
the limits for a Class A digital device, pursuant to both part
15 of the FCC Rules and the radio interference regulations
of the Canadian Department of Communications: These
limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses
and can radiate radio frequency energy and, if not instal-
led and used in accordance with the instruction manual,
may cause harmful interference to radio communications.
Operation of this equipment in a residential area is like to
cause harmful interference in which case the user will be
required to correct the interference at his own expense.
10. Dimensional drawing
112.5
114.1
Fig. 8. Housing type P13/70 clipped onto a top-hat rail
(35 ×15 mm or 35×7.5 mm, acc. to EN 50 022).
10
11
12 13
1
2
3
4 5
6
7
8
9
70
11