esera automation 11216 사용자 설명서 - 페이지 2
{카테고리_이름} esera automation 11216에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. esera automation 11216 9 페이지. 8-fold digital input for 1-wire bus
esera automation 11216에 대해서도 마찬가지입니다: 사용자 설명서 (7 페이지)
1
Product description
The 8-fold Digital Input Module can be used to query the status of 8 switches, reed contacts or all kinds of digital
sensors. The LED indicators on the front panel show the status of the switch inputs. When the input voltage is
present, the respective LED indicator lights up.
To protect the inputs additionally against disturbances, the module has filters with a delay of only 30ms.
Each input can be set manually by pushbutton for test purposes, maintenance or development.
The inputs are isolated from the 1-Wire Network by Optocouplers. This allows very long connection cables
between the module and the sensors without interfering with the 1-Wire Bus.
In addition, the isolation between switch inputs and 1-Wire Network provides increased safety.
For the operation of the Module only a 2V supply voltage is necessary. For this, we recommend the use of one
of our 1-Wire Hub module.
Note
Basics and Tips on the 1-Wire Bus system can be found in the ESERA Online Shop under
1-Wire Basics or please refer to our eBook in the shop under Training/Documentation.
2
Technical Data
Number and Type
Input voltage
Filter
LED displays
Data interface
Auto-E-Connect
Support
Operating voltage
Current
consumption 12V
Internal fuses
Insulation voltage
Connection
Note
Only a 12V supply voltage is required to operate the module.
For power supply we recommend a 1-Wire Hub device. Input voltages above 30V can cause permanent
damage to the module.
3
Ambient conditions
Temperature,
Operation
Air humidity
Dimensions
Protection class
Protection system
Auto-E-Connect
Support
Insulation
resistance
*if the sensor or actuator supports Auto-E-Connect. For details, please refer to the operating instructions of the sensor or actuator.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de
8 inputs for DC voltage signals 10 - 30VDC
max. 30 VDC, max.8mA, low level: <5V high level 10-30V
Software filter against switch bounce (30 ms delay)
10 LEDs (Power LED, Status LED, 8 x Input)
Input LED lights up at status high of the 1-Wire DS2408 interface
1-Wire Bus (12V, Data and ground), DS2808 command set
Level I to II
12VDC (+/-10%)
12V: max. 40mA, all inputs active
no changeable fuses available
min. 500VAC against 1-Wire Bus
srew terminals (up to 2,5qmm cable cross section)
-10°C to +50°C
10 - 92% (non condensing)
32 x 90 x 70mm (WxHxD)
II
IP20
Level I to II
500VAC inputs to 1-Wire Bus
11216 V5.0 R1.0 Manual
Page 2 of 9